Power grids from Europe to Australia dip slightly every 60 seconds. A new Nature Energy study traced the pulse to backup batteries that run their self-tests at the top of every minute.
Every minute, right on the minute, the power grid hiccups. You’ll never see it in your lights. Grid operators saw it in their data, and for years nobody could explain it.
German researchers now say the culprit is backup batteries checking on themselves, all at once.
Their study came out Friday, Oct. 30, in the journal Nature Energy. ScienceAlert covered it Tuesday, Nov. 10.
“That was really years of detective work,” physicist Dirk Witthaut said in a statement from Forschungszentrum Julich, the German research center where he works. The quote is translated from German. Carsten Hartmann is the lead author, and researchers from the University of Cologne and the Karlsruhe Institute of Technology also took part.
The wobble is tiny. ScienceAlert reported that it’s usually just a few millihertz and poses no immediate threat.
Watch the Clownfish TV podcast on YouTube. Article continues below.
Where does the 60-second pulse show up?
Nearly everywhere the team looked. ScienceAlert named the grids of continental Europe, Britain, Scandinavia, Australia and the United States. Those grids aren’t connected, so one can’t be passing the pulse to the next.
The German science magazine Bild der Wissenschaft reported that the signal is strongest in Europe, North America and Australia. It also turns up in smaller grids in Malaysia, South Korea and South Africa.
The pulse itself is old news to engineers. Researchers first documented it in Scandinavia around 2014, according to ScienceAlert. Tennet, Germany’s largest transmission grid operator, had also watched the European grid’s frequency dip every 60 seconds for several years, Julich said.
How did scientists trace it to backup batteries?
They started by wiring up their own workplace. The team installed measuring devices at 80 points on Julich’s campus, and the one-minute pattern appeared only in buildings with uninterruptible power supplies, known as UPS units.
“It was quickly clear to us that the cause must be something controlled by a clock,” Witthaut said.
One unit gave the game away. “We looked at one of them more closely and found a power spike at the start of every minute due to the power query,” he said. The manufacturer confirmed the spikes came from automatic battery self-tests, ScienceAlert reported.
Why would thousands of batteries test at the same second?
They all keep very good time. A UPS is a big battery that keeps hospitals and data centers running when the power cuts out, and its software checks that battery on a schedule.
No binding standard sets that schedule, according to Julich. Manufacturers apparently settled on every 60 seconds, starting at the top of the minute.
Many of these devices set their clocks by external time signals, ScienceAlert explained. So machines that have never heard of each other draw extra power in lockstep. “The observed effect can only be produced if many devices draw power at the same time,” Witthaut said.
Is the 60-second pulse a problem for the power grid?
There’s no urgent danger, according to the researchers. The trouble is that the pulse keeps getting bigger. In Ireland, where data centers use about one fifth of the country’s electricity, the size of the one-minute signal quadrupled between 2016 and 2021, Julich said.
It’s already wearing things out. The paper says the pattern is “contributing to wear and tear in hydropower systems.” It has also pushed grids toward stricter frequency-control rules, the authors write. Bild der Wissenschaft reported that Scandinavian operators tightened their rules after the pulses wore out hydropower turbines faster.
The authors summed up the lesson in a line ScienceAlert quoted. “Even benign control routines can become systemically relevant when many devices act coherently.”
Could dishwashers and heat pumps be doing it too?
Maybe. “It is quite possible that battery storage is only part of the problem here,” Witthaut said.
He added that it can’t be ruled out that other digitally controlled devices show similar patterns. His examples were air conditioners, heat pumps, washing machines and dishwashers. The paper warns that the spread of battery storage, data centers and internet-connected gadgets “may further amplify” these power swings.
How do you fix a grid’s heartbeat?
Shuffle the schedule. “One would simply have to distribute the queries randomly, rather than starting them all at the same time,” Witthaut said.
At least one company is already on it. ScienceAlert reported that one manufacturer, which it didn’t name, pushed a software update that loosened the strict timing of its system checks.
So the grid’s strange heartbeat came down to some very punctual batteries. The cure is teaching them to run a little late.
Article compiled and written by Thom Pratt (editor-in-chief), Derek Gibbs (beat editor) and the Clownfish TV newsroom.
D/REZZED is part of Clownfish TV. For more news, views, and rants on gaming, tech, and pop culture, subscribe at clownfishtv.com. Watch the show on YouTube at @ClownfishTV where new episodes drop daily. Subscribe to the Clownfish TV podcast on Apple Podcasts, Spotify, iHeart, and wherever else you get your podcasts.
Hat Tips:
-
ScienceAlert, Michelle Starr (Nov. 10): The findings and the manufacturer’s update.
-
Nature Energy, Hartmann, Witthaut et al. (Oct. 30): The paper.
-
Forschungszentrum Julich via Solarserver (Oct. 30): Witthaut’s quotes and the Ireland figures.
-
Bild der Wissenschaft, Nadja Podbregar (Nov. 2): Affected grids and turbine wear.
AI Disclosure: All articles are assigned, edited and reviewed by an experienced human editor before posting. Like most modern newsrooms, WebReef Media uses a variety of AI tools to help with accuracy and efficiency. Ways AI may be used in article creation include research, grammar, fact-checking and ideation, as well as occasional AI generated or enhanced thumbnails or graphics. No articles are generated or posted without human oversight or involvement.